RIKA KOGYO Industrial Partner

REX-D400 - Rika Kogyo REX-D400 Digital Temperature Controller - Less than 12VA...

larger image

Request Quote
For Price
Part Number:
REX-D400
Model Number:
REX-D400
Make:
RIKA KOGYO
Lead Time:
Available
Qty In Stock:
Available

Rika Kogyo REX-D400 Digital Temperature Controller - Less than 12VA (100 to 240V AC) power, ± (0.3% of span + 1 digit) accuracy, Standard universal inputs and outputs Simple Type: PLC Thermocouple Module

The D series controller features wide variety of functions, such as fuzzy logic algorithm, universal input/output, retransmission and digital communication. The D series controller eliminates bothersome modifications, and is ideal for applications to which simple standard controller does not fit.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • Fuzzy logic algorithm
  • Ramp rate setting of setpoint change
  • Retransmission
  • Standard universal inputs and outputs
  • Two setpoints

Specifications

    General
  • 1500V AC for one minute between power terminals and ground
  • b) 21.6 to 26.4V AC(Including supply voltage variation) [Rating : 24V AC] (50/60Hz common)
  • b) Alarm action : Programmable (process, deviation, SV, FAIL)
  • b) Communication speed : 1200, 2400, 4800, 9600, 19200 bps
  • b) CT type : CTL-6-P-N (30A), CTL-12-S56-10L-N (100A)
  • b) Heat/cool PID control with autotuning and fuzzy logic
  • b) LBA deadband : 0 to 9999ºC [ºF] or 100% of span (OFF by setting zero)
  • b) Output signal : 0 to 5V, 0 to 10V, 1 to 5V DC (Load resistance : More than 1kW), 0 to 20mA, 4 to 20mA DC (Load resistance : Less than 600W)
  • c) 21.6 to 26.4V DC(Ripple rate 10% p-p or less) [Rating : 24V DC]
  • c) Alarm differential gap : -10 (-10.0) to 10 (10.0)
  • c) Bit format: Start bit : 1, Data bit : 7 or 8, Parity bit : Without, Odd or Even
  • c) Display range : 0.0 to 100.0A (OFF by setting Zero)
  • Continuous voltage output : 0 to 5V, 0 to 10V, 1 to 5V DC (Load resistance :More than 1kW)
  • Cool-side proportional band : 1 to 3000% of heat-side proportional band(Heat/cool ON/OFF action when Pc-0)
  • Current output : 0 to 20mA, 4 to 20mA DC (Load resistance :Less than 600W)
  • d) Accuracy : ± 5% of input value or 2A (whichever is larger)
  • d) Alarm delay : 0 to 600 sec.
  • d) Communication code : ASCII(JIS) 7-bit code
  • DC voltage, DC current : -1999 to 9999(A decimal point position is the same as that of PV.)
  • Deadband/Overlap : -10(-10.0) to 10(10.0) ºC(ºF) (Temperature input), -10.0 to 10.0% of span (Voltage, current input)
  • Derivative time : 1 to 3600sec.(P + I action when D-0)
  • Heat-side proportional band : 1(0.1) to setting limit high.(ON/OFF action when P-0)
  • Influence of external resistance: Approx. 0.4µV/W
  • Influence of input lead : Approx. less than 10W
  • Input break action : Down-scale
  • Input break action : Down-scale, A 250W resistor is externally connected.
  • Input break action : Up-scale
  • Input break action : Up-scale
  • Input break action : Up-scale
  • Integral time : 1 to 3600sec.(P + D action when I-0)
  • Less than 200mA (24V DC)
  • Less than 7.5VA (24V AC)
  • Manual control : -5.0 to +105.0% (Heat/cool control type : -105.0 to +105.0%)
  • More than 20MW (500V DC) between power terminals and ground
  • Not available for heat/cool control type.
  • OUT1 of D400/D900 : 0/15V DC (Load resistance :More than 1KW)
  • Output from ALM1 terminal
  • Output from ALM2 terminal
  • Output limiter high : -5.0 to +105.0%
  • Output limiter low : -5.0 to +105.0%
  • Proportional cycle time : 1 to 100 sec.
  • REX-D400/900: Standard function, REX-D100: Optional function
  • Type : SV1/SV2 selection (open : SV1, close : SV2)
  • Voltage pulse output : 0/12V DC (Load resistance :More than 600W)
  • a) Thermocouple: K, J, R, S, B, E, T, N (JIS/IEC), PLII (NBS), W5Re/W26Re (ASTM), U, L (DIN)
  • Alarm output: Relay output, Form A contact 250V AC 0.5A (resistive load)
  • Analog output: a) Number of outputs : 1 point
  • b) RTD: Pt100 (JIS/IEC), JPt100 (JIS)
  • c) DC low voltage input: 0 to 10mV, 0 to 100mV, 0 to 1V
  • Cold-junction temperature compensation error: Within ±1.5ºC (between 0 and 50ºC [32 and 122ºF])
  • Control loop break alarm: a) LBA time setting : 0 to 7200 sec. (LBA OFF by setting Zero)
  • Control method: a) PID control with autotuning and fuzzy logic
  • Control output: Relay output : Form C contact, 250V AC 3A (resistive load)
  • d) DC high voltage input: 0 to 5V, 1 to 5V, 0 to 10V
  • Data retaining period: Approx 10 years (depends on storage and operating conditions.)
  • Dielectric strength: 1000V AC for one minute between input terminals and ground
  • Digital communications: a) Communication method : RS-485 (2-wire), RS-422A(4-wire)
  • e) DC current: 0 to 20mA, 4 to 20mA
  • Effect by power failure: A power failure of 20 msec or less will not affect the control action.
  • External contact input: Number of inputs : 1 point.
  • External Dimensions (W x H x D): 48 x 96 x 100mm
  • Heater break alarm (Optional): a) Number of inputs : 1 or 2 points.(2 points for 3-phase heater)
  • Insulation resistance: More than 20MW (500V DC) between input terminals and ground
  • Major setting range: Setting range : Same as input range.
  • Measuring accuracy: ± (0.3% of span + 1 digit)
  • Memory backup: Backed up by EEP-ROM.
  • Operating environments: 0 to 50ºC [32 to 122ºF] , 20 to 80% RH
  • Power consumption-: Less than 12VA (100 to 240V AC)
  • PV bias: Temperature input : -1999(-199.9) to 9999(999.9)ºC[ºF]
  • Sampling time: 0.5 sec
  • Supply voltage: a) 90 to 264V AC (Including supply voltage variation) [Rating : 100 to 240V AC] (50/60Hz common)
  • Temperature alarm: a) Number of alarms : 2 points
  • Weight Approx.: 250g

 

Applications

  • None Available

Aliases